Ningbo Tianan(Group) Co.,Ltd.
|
Payment Terms: | FOB Ningbo |
Place of Origin: | Zhejiang, China (Mainland) |
![]() |
|
Add to My Favorites | |
HiSupplier Escrow |
No.
|
Item
|
Unit
|
Data
|
||||
1
|
Rated voltage( that is Max working voltage)
|
kV
|
12
|
||||
2
|
Rated insulation level
|
1min power frequency withstand voltage,
|
kV
|
42
|
|||
Lightning impulse withstand voltage
|
kV
|
75
|
|||||
3
|
Rated frequency
|
Hz
|
50
|
||||
4
|
Rated current of main busbar
|
A
|
630
|
1250
|
2000 2500 3150
|
||
5
|
Rated current of branch busbar
|
A
|
630
|
1000 1250
|
2000 2500 3150
|
||
6
|
4s short-time withstand current
|
kA
|
20
|
31.5
|
40
|
||
7
|
Rated peak withstand current
|
kA
|
50
|
80
|
100
|
||
8
|
Protection degree
|
|
IP3X
|
||||
9
|
Dimension(width*depth*height)
|
mm
|
900x1050x2300
|
1000x1050x2300
|
|||
No.
|
Type
|
ZN28B-12/¡õ-31.5(20)
|
ZN28B-12/¡õ-40
|
|||||
1
|
Rated voltage (kV)
|
12
|
||||||
2
|
Rated current (A)
|
630
|
1250
|
2000
|
1600
|
2500
|
3150
|
|
3
|
Lightning impulse withstand voltage (kV)
|
75
|
||||||
4
|
Power frequency withstand voltage (kV)
|
42
|
||||||
5
|
Rated frequency (Hz)
|
50
|
||||||
6
|
Rated short circuit breaking current (kA)
|
20
|
31.5
|
40
|
||||
7
|
4s short-time withstand current(kA)
|
20
|
31.5
|
40
|
||||
8
|
Peak withstand current (kA)
|
50
|
80
|
100
|
||||
9
|
Breaking current of capacitor bank (A)
|
400
|
||||||
10
|
Short circuit making current(kA)
|
50
|
80
|
100
|
||||
11
|
Rated operating sequence
|
0-0.3s-CO-180s-CO
|
||||||
12
|
Mechanism fitted
|
CD17-I
|
CD17-II
|
CD17-III
|
||||
CT19-I
|
CT19-II
|
CT19-III
|
||||||
13
|
Mechanical endurance
|
10000 times
|
10000 times
|
|||||
14
|
Breaking times of rated short circuit
|
500
|
30
|
|
||||
15
|
Breaking times of rated current
|
10000
|
10000
|
|||||
16
|
Main circuit resistance (¦Ì¦¸)
|
<=35
|
<=25
|
|||||